Model: NL-DXF-1
The problem
A four-way valve for a household air conditioner costs about a thousand yuan; the one on a commercial chiller is dozens of times larger - 6000-20000kg/h of flow, flanges up to 4-1/4 inch, reversal differential tested to 30bar. Such a valve simply does not fit a small bench: the pipe size does not match, flow is insufficient and differential pressure cannot be built up, so shipment inspection is limited to appearance and static tightness. When the valve later sticks or leaks excessively inside a magnetic-bearing or screw chiller, the loss is the commissioning schedule of the whole unit.
Capability
This bench is built for that scale. Flow capacity of 6000-20000kg/h covers the flow range of screw chiller four-way valves and is read directly on a mass flow meter rather than converted from volumetric flow. Pressure reaches 4.0MPa and both the 30bar maximum and 1bar minimum reversal differential can be established and held. Flange interfaces cover 2-5/8, 3-1/8, 3-5/8 and 4-1/4 inch with quick-change fixtures supplied to the sample drawing, so a model change needs no pipe rework. A dedicated electronic expansion valve branch measures flow characteristics at the 5-6kg differential of screw chiller operation and reports full pulse count, five forward and reverse flow points and internal leakage. Endurance testing runs at 85 percent rated coil voltage with a 1-500,000 cycle counter and power-off memory so an interruption does not restart the run. Water and nitrogen media are both supported: a thermostatically controlled water loop (plate exchanger at 5-45C) and a gas side for tightness and hydraulic proof, covering the main type-test items on one machine. Test items are grouped - flow characteristic, reversal differential (max and min), internal leakage, hydraulic proof with 3min hold, and high/low differential endurance - with reports archived by valve model. The return loop is closed so test water is reused and long endurance runs need no repeated filling, and the variable-speed pump approaches the target flow smoothly instead of throttling a valve.

Key specifications
- Valves: screw and magnetic-bearing chiller four-way valves, electronic expansion valves
- Flow range: 6000-20000kg/h (four-way valve flow capacity)
- Pressure range: up to 4.0MPa
- Reversal differential: 30bar maximum, 1bar minimum
- Flanges: 2-5/8, 3-1/8, 3-5/8, 4-1/4 inch with quick-change fixtures
- Expansion valve differential: 5-6kg at screw chiller conditions
- Media: water (thermostatic loop) and nitrogen (tightness, hydraulic proof)
- Media temperature: 5-45C controlled by plate exchanger
- Flow measurement: mass flow meter covering 6000-20000kg/h
- Differential measurement: transmitter across the valve, 1-30bar
- Coil drive: 0-300V variable, 85 percent rated voltage reversal
- Endurance counter: 1-500,000 cycles with power-off memory
- Test items: flow characteristic, reversal differential, internal leakage, hydraulic proof 3min, high/low differential endurance
- Data: flow, upstream and downstream pressure, differential, media temperature, reversal count; curves and reports
Applications
Incoming inspection and type testing of valves at commercial and central air-conditioning plants; development validation of large-size four-way and electronic expansion valves at valve manufacturers; whole-unit matching tests for magnetic-bearing and screw chillers; commissioned valve testing at third-party laboratories
About the manufacturer
Guangdong Endurance Electronic Equipment Co., Ltd provides non-standard customization, drawing confirmation, factory acceptance, on-site installation and commissioning, operation training and long-term technical service; 12-month warranty and long-term spare parts supply. Tel: 0760-88500902 / 13416787649. Web: en.zsnaili.com.
Applicable standards
Test items and methods refer to the relevant clauses of JB/T 10212 (direct-acting electronic expansion valves for air conditioning) and JB/T 8592 (solenoid four-way reversing valves for household and similar air conditioners), with ranges extended for large chiller valves. Proof pressure, hold time and acceptance values follow the customer technical agreement and the valve drawing.